Product introduction
    
        - 
            01 Product application 
			
				It is suitable for buildings with higher fire safety requirements due to high concentration of people, high value material and cultural assets (skyscrapers, hospitals, shopping, tunnels, museums, cinemas, theatres). Cables can be used for power supply
or control (lighting, elevators, fire fighting equipment, pumps). They can be used for fixtures in buildings. In the case of outdoor applications, the cable should be protected against ultraviolet radiation and external factors.
            
            
                 
            
            
         
        - 
            02 Product characteristics  
			
				No halogen
        corrosive and toxic gases
			
			
				Flame retardant
self-extinguish
Flameless propagation
Non-spontaneous combustion
			
         
        - 
            03 Technical certification ·Conform to RoHS standard
·CE certification = Products comply with EC Low Voltage Directive 2006/95/EG.
            
         
    
    
    
 
    Product structure
    
        Conductor material: bare copper wire
    
    
        Fire protection layer: flame retardant mica tape
    
    
        Insulation: cross-linked halogen-free compounds
    
    
        Insulation refractory :FE180- 180 minutes of insulation integrity under the direct influence of flame
    
    
        Insulation color: digital coding core and above can be added yellow-green
    
    
        Inner sheath: halogen-free
    
    
        Outer sheath: halogen-free polymer
    
    
        Jacket color: Orange/customizable
    
    
        Rated voltage :0.6/1kV
    
    
        Test voltage :4kV
    
    
        Small bending radius :Ø:15xd
    
    
        Temperature rating :-30°C/+90 °C
    
    
        Circuit Integrity: Available as E30 /E90- Ensures functional integrity for 30 minutes /90 minutes
    
    
        Halogen-free: According to IEC 60754-1 standard
    
    
        Smoke density: According to IEC 61034 standard
    
    
        Flame retardant: According to IEC 60332-2 standard
    
    
        Product ID :Aein beke SHANGHAI AEIN WIRE & CABLE CO.,LTD Model Specification Voltage CE meter standard